I – Parameter definition
S900–II Configuration
Version 2.1
45
01T01506_1
25.11.99
INTERFACE INPUTS WITH INJECTION MOULDING MACHINE 1
Possible value : 0 –> 255 Specific values : 127 –> forced to 0
128 –> forced to 1
PARAMETER Abbreviation Description Default
value
Function
0490
IN_FIN_MV_
NOY_1_1
End of core puller
movement 1
10 Input at 1 if IMM 1’s core pullers have reached position 1.
0491
IN_FIN_MV_
NOY_2_1
End of core puller
movement 2
11 Input at 1 if IMM 1’s core pullers have reached position 2.
0492
IN_EJECT_OUT1
Ejectors out 9 Input at 1 if IMM 1’s ejectors are out.
0493
IN_EJECT_IN_1
Ejectors in 8 Input at 1 if IMM 1’s ejectors are in.
0494
IN_FIN_OUVERT
1
Mould open 7 Input at 1 if IMM 1’s mould is completely open.
0495
IN_PIECE_FAB_1
Mould closed 14 Input at 1 if IMM 1’s mould is closed.
0496
IN_PORTE_
CLOSE_1
Gate closed 128 Input at 1 if IMM 1’s gate is closed.
0497
IN_OUV_
PARTIELLE_1
Partial opening reached 15 Input at 1 if IMM 1’s mould is partially open (descent is authorized).
0498
IN_AUTO_MACH
1
Machine in Automatic or
Semi–Automatic
13 Input at 1 if IMM 1 is in automatic or semi–automatic.
0499
IN_CTL_
RELANCE_1
Anticipated restart control
input
127 Input at 1 if the anticipated restart’s monitoring circuit is active. If this is the
case, the D_35: ANTICIPATED RESTART NOT CONFORM fault
appears on the screen. To reactivate the monitoring circuit, power down the
robot cabinet.
The default value may vary depending on the type of input / output board. Consult the list of robot parameters, file S.