Conair FC-33 Podręcznik Użytkownika Strona 42

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 58
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 41
Example
The granulator is equipped with a current sensing relay to control a conveyor.
A motor of 7.5 kW has a rated current of about 15 A.
When this star/delta is started, it pulls about 15 A/ i.e. about 9 A per phase.
Relay setting:
Motor size 15 A/ = 8,7 A per phase
T1 Ð Start delay setting 0.1 second.
T2 Ð Reaction time setting 3.0 seconds.
A Ð Hysteresis 20 %.
B Ð Limit value 30 %.
C Ð Relay function N normal.
The current transformer size is 30/1A.
The current transformer is connected to E2 (1 A).
In a current transformer with a transformation ratio of 30/1, the limit value B
should be set to 30 % or 9 A (30 A = 100 %).
The current sensing relay detects the current consumption of the granulator
motor and stops the conveyor, when the granulator motor exceeds 9 A for
3 seconds, to prevent further material from being fed into the hopper.
The relay re-starts the conveyor automatically when the granulator motor con-
sumption has fallen 20 % below 9 A, i.e. to 7 A without a time delay.
CF Series Granulators UGG003/0398
38 WIRING
A T2 B
C T1
Przeglądanie stron 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 57 58

Komentarze do niniejszej Instrukcji

Brak uwag